Product Description
The HG110-D, a triple-listed thermostatic mixing valve, delivers water at a safe 120°F (49°C) or lower from all outlets, while allowing the water heater to be set at a germ-killing 140°F (60°C) or higher which aids in preventing the growth of legionella bacteria in the water heater. The higher tank temperature means that hot water demands can be satisfied longer. Robust, low complexity construction. Every valve is tested for performance prior to shipping. Adjustable and lockable mechanism minimizes unauthorized tampering with valve setting. Each heatguard valve is factory set and locked to a maximum 120°F (49°C). Adj. outlet temperature range: 85-130°F (29-54°C)
Typical Applications
Domestic and Commercial hot water distribution. To control water temperature at the source of heat (hot water tank), point-of-use (sinks, lavatories, or bath tubs) or multiple fixtures (multiple sinks)
Features
- Size: 1'' Sweat
- High flow rate design for lower pressure losses within the system
- Every valve is tested prior to shipping
Performance:
Outlet temperature range . . . . . 90 - 130 °F (32 - 54 °C)
Temp. hot supply . . . . . . . . . . . 195 °F (90 °C) max.
Temp. cold supply . . . . . . . . . . . 39 - 80 °F (5 - 27 °C)
Temp. stability . . . . . . . . . . . . . . +/- 5 °F (3 °C)
Working pressure . . . . . . . . . . . Max. 145 psi (1,000 kPa)
Flow rate, minimum . . . . . . . . . . 1.0 gpm
Flow rate, maximum . . . . . . . . . 20 gpm
Size: 1 Brand: SharkBite